High-flow above-ground fire hydrant
Patent No.: ZL202120360765.1 (Structure)
ZL201930728754.2 (Design)
Keywords:
firefighting equipment
Category:
Petroleum Industry-Specific Outdoor Fire Hydrant
E-mail:
Detailed introduction
Patent No.: ZL202120360765.1 (Structure), ZL201930728754.2 (Appearance)
Firefighting-specific for petrochemical enterprises
Complies with the requirements of GB60160 (2018 edition) regarding the installation of high-flow fire hydrants in petrochemical enterprises.
Usage: Installed along both sides of roads on fire hydrant lines, primarily designed to supply water to fire trucks or enable high-flow water intake from multiple points.
Scope of application:
"Stable High-Pressure" Fire Water System for Petrochemical Enterprises—Dedicated Products for Unit Areas and Tank Farms
Product features:
● Multiple outlets, high throughput
● Each outlet has its own control valve for convenient use.
● Equipped with a DN150 fire truck suction hose interface for faster water supply to fire trucks
● Dual-plunger drain valve automatically removes residual water from the cavity after the fire hydrant main valve is closed, preventing freezing in winter.
● The main transmission components and seals are made from copper alloy and S30408 material, offering superior corrosion resistance.
● The main valve features a pressure-reducing sealing design, ensuring that the opening force remains unaffected by system pressure.
● JOTUN paint, lasting three years without fading
● Equipped with anti-collision functionality: Even after being damaged by impact, the main valve remains closed, allowing for pressure-rated replacement of the damaged component through above-ground operations.
Main technical parameters:
| Name |
High-Flow Above-Ground Fire Hydrant (Impact-Resistant, Pressure-Regulating) |
|
| Model |
SSLF200/200-1.6 |
SSLF250/270-1.6 |
| Nominal specification (mm) |
DN200 PN1.6 MPa |
DN250 PN1.6 MPa |
| Working pressure range (MPa) |
0.5–1.6 |
0.5–1.6 |
| Flow Range (L/S) |
150–200 |
200–270 |
| Water outlet connection (model × quantity) |
2 units of KWS65 and 2 units of KWS80 |
KWS80 × 4 units |
| Water intake interface specifications (mm) |
M125×6 |
M170×6 |
| Automatic drain outlet specifications (m) |
Ø18 × 2 - Plunger Valve Design |
|
| Inlet Flange Specifications |
DN200 PN1.6-RF |
DN250 PN1.6-RF |
| Flange Standards |
HG/T20592-2009 (GB/T9124.1~2 or ANSI and ASME) |
|
| Total height range (m) |
1.3–4.5, choose any |
|
| Applicable Medium |
Freshwater or neutral water. If it's seawater, additional anti-corrosion treatment is required. |
|
Pressure-regulating above-ground gauge-equipped, dual-drainage pressure regulating valve – KB
Online Message