PRODUCTS CENTER
Pressure-regulating above-ground gauge-equipped, dual-drainage pressure regulating valve – KB
Patent No.: ZL201620234704.X
Keywords:
firefighting equipment
Category:
Petroleum Industry-Specific Outdoor Fire Hydrant
E-mail:
Detailed introduction
Patent No.: ZL201620234704.X
Dedicated to the stable high-pressure firewater system for petrochemical enterprises
Scope of application:
Specialized products for the "Stable High-Pressure" firewater system in petrochemical enterprises
Product features:
● Quick operation: Simply rotate the wrench 4/5 of a turn to fully open or close it.
● Stepless Pressure Adjustment: The rotation angle of the wrench determines the output pressure, allowing for flexible customization.
● Piston-type drain valve automatically removes residual water from the cavity after the fire hydrant is shut off, preventing freezing in winter.
● The main valve features pressure-assisted sealing— the greater the pressure, the better the seal.
● Equipped with a pressure gauge that displays the instantaneous pressure inside the fire hydrant.
● Made from premium materials, offering superior rust-resistant performance
● JOTUN paint, lasting three years without fading
Main technical specifications
| Name |
Quick-Acting Above-Ground Fire Hydrant (Dual Drain, with Pressure Gauge) |
||
| Model |
SST100/65-1.6KB |
SST150/65-1.6KB |
SST150/80-1.6KB |
| Nominal Specification |
DN100PN1.6MPa |
DN150 PN1.6 MPa |
|
| Water outlet model × quantity |
KWS65 × 2 units |
KWS65 × 2 units |
KWS80 × 2 units |
| Inlet Specification – Standard Thread |
M125×6 |
M170×6 |
|
| Pressure gauge model specifications |
YTN-40Z × 2.5 MPa model, made from S304 material, with vibration-resistant and weatherproof features (-50°C to +80°C). |
||
| Automatic drain outlet specifications |
Piston-type, Ø12 × 2 units |
||
| Inlet Flange Specifications |
DN100 PN1.6-RF |
DN150 PN1.6-RF |
|
| Inlet Flange Standard |
HG/T20592-2009 (GB/T9124.1~2 or ANSI and ASME) |
||
| Total height range (m) |
0.7–3.5 m, choose as you like |
Choose from 0.8 to 4.8 meters |
|
| Applicable Medium |
Freshwater or neutral water. If it's seawater, additional anti-corrosion treatment is required. |
||
Pressure-regulating above-ground gauge-equipped, dual-drainage pressure regulating valve – KB
Online Message
Please leave your phone number or email address, and we will contact you within 24 hours